Yeah, some politician got some "duh, stupid engineers" points out of that sentence. Completely ignoring the fact that the original design also pulled smoke down and was considered to be fine. Since these systems are active and suck the smoke out up or down doesn't matter all that much.
From the third paragraph: "Smoke evacuation canals designed to suck out smoke and replace it with fresh air failed to do either. In an actual fire, the inspectors determined, the main smoke vent might well implode." Assuming the inspectors were correct, the original design, at least as implemented, didn't work. While the "in accordance with the laws of physics" may be overly catty, a bit of searching around suggests…
The original design was never tested, because the building as originally designed never existed.
Each addition ordered up by Schwarz required shifting passenger flows through the terminal. That meant rebuilding walls, exits, emergency lights, ventilation systems, windows, elevators, and staircases. At one point, in 2009, outside controllers urged Schwarz and his engineering chief to shut down construction for half a year to give the architects and contractors time to coordinate efforts.
That never happened, so there never was a complete design for the changed building, and the fire system wasn't properly replanned for the new situation. Which lead to issues like the collapsing pipes: They fitted stronger fans, but no-one realized that the pipes can't hold the higher pressure difference.