Worst case at 240v : Electric hot water heater = 20 amps Electric stove = 50 amps all burners on and oven Washing machine = 15 amps Car charger = 50 amps Total = 135 amps Standard residential service in the US = 200 amps split phase @ 240v Whats the problem?
All the other 15 amp circuits people take for granted for things like lights, the clothes dryer and the heat/cooling system you left off your list (heat pump + air handler + emergency heat coils)... Add in the 80% rule and 200amps doesn't go as far as one might hope in a gas free-house.
Requiring new builds to have even more electrical capacity and more robust incoming infrastructure is a win-win-win situation and hopefully that is what code & consumers demand.